FNZ-II generator rotor AC impedance and power loss tester is a new generation of enhanced AC impedance tester based on FNZ-I type improved and improved by Yangzhou Fukete Electric Co., Ltd., adopting advanced The “one-touch shuttle†(rotary mouse) technology makes the operation simple and convenient, and cancels the conventional controls such as the panel buttons. The instrument adopts the advanced high-speed microprocessor technology of today's Zui, with more powerful functions and superior performance. It has the characteristics of high work reliability, easy operation, high test accuracy, small size and lightness. Currently in the country at the lin first level.
Notes on the use of generator rotor AC impedance tester 1. Before using the instrument, carefully read the product instruction manual and master the correct use method.
2. Correct wiring during the test. Power can be supplied after checking that the wiring is correct and the connection is reliable.
3. Among the two wires of the test tong, the slightly thicker wires are current wires (I1, I2), and the slightly thinner wires are voltage wires (U1, U2). This instrument uses a special high-current quick connector, which should be rotated slightly when plugging and unplugging.
4. Correct operation. During the test, the regulator should be evenly and slowly boosted near the test point to ensure the reliability of data acquisition.
5. If there is a protective action during the test, it is necessary to find out the cause of the abnormality before continuing the test. Do not operate blindly to avoid unnecessary losses.
Notes on the use of generator rotor AC impedance tester 1. Before using the instrument, carefully read the product instruction manual and master the correct use method.
2. Correct wiring during the test. Power can be supplied after checking that the wiring is correct and the connection is reliable.
3. Among the two wires of the test tong, the slightly thicker wires are current wires (I1, I2), and the slightly thinner wires are voltage wires (U1, U2). This instrument uses a special high-current quick connector, which should be rotated slightly when plugging and unplugging.
4. Correct operation. During the test, the regulator should be evenly and slowly boosted near the test point to ensure the reliability of data acquisition.
5. If there is a protective action during the test, it is necessary to find out the cause of the abnormality before continuing the test. Do not operate blindly to avoid unnecessary losses.